What occurs if the load is removed from an operating series DC motor?

  • It will stop running.
  • Speed will increase slightly.
  • No change occurs.
  • Correct Answer
    It will accelerate until it falls apart.

What occurs if the load is removed from an operating series DC motor?

It will accelerate until it falls apart.

When a substantial amount of current is applied to a DC motor at start - has no emf resistance (back emf), then the rotation will increase quickly, and without anything to slow it down, it will accelerate past the hardware tolerances, causing damage.

For more info, please see Sluiceartfair site for the article on What will happen to a DC series motor when its load is removed?

Last edited by markadlerdallas. Register to edit

Tags: none

If a shunt motor running with a load has its shunt field opened, how would this affect the speed of the motor?

  • It will slow down.
  • It will stop suddenly.
  • Correct Answer
    It will speed up.
  • It will be unaffected.

If a shunt motor running with a load has its shunt field opened, how would this affect the speed of the motor?

It will speed up.

From: wp2ahg

  • A shunt wound motor has a high-resistance field winding (a 'shunt') in parallel with the motor.

  • So, it passes some of the circuit's energy around the motor and through the field winding (shunt) to limit the motor's speed.

  • Removing the shunt would remove that speed control causing an increase in the motor's rpms. It will speed up.


To fully understand the behavior of shunt DC motors the key concept is "armature" which is kind of like torque in a car.

It has key variables such as Pole Pitch (back and front pitch, resultant pitch and communicator pitch, Coil Span, Commutator Pitch. Please see Electrical 4 U site for article on Armature Windings: Pole Pitch, Coil Span And Commutator Pitch

And, for information on DC shunt motors, please see Electrical 4 U article on DC Shunt Motor: Speed Control, Characteristics & Theory

Last edited by markadlerdallas. Register to edit

Tags: none

The expression “voltage regulation” as it applies to a shunt-wound DC generator operating at a constant frequency refers to:

  • Correct Answer
    Voltage fluctuations from load to no-load.
  • Voltage output efficiency.
  • Voltage in the secondary compared to the primary.
  • Rotor winding voltage ratio

The expression “voltage regulation” as it applies to a shunt-wound DC generator operating at a constant frequency refers to:

Voltage fluctuations from load to no-load.

Basically, the speed will increase, decrease, and increase. For information on DC shunt motors, please see Electrical 4 U article on DC Shunt Motor: Speed Control, Characteristics & Theory


From: wp2ahg

  • A shunt wound motor has a high-resistance field winding (a 'shunt') in parallel with the motor.

  • So, it passes some of the circuit's energy around the motor and through the field winding (shunt) to limit the motor's speed.

  • Removing the shunt would remove that speed control causing an increase in the motor's rpms. It will speed up.


To fully understand the behavior of shunt DC motors the key concept is "armature" which is kind of like torque in a car.

It has key variables such as Pole Pitch (back and front pitch, resultant pitch and communicator pitch, Coil Span, Commutator Pitch. Please see Electrical 4 U site for article on Armature Windings: Pole Pitch, Coil Span And Commutator Pitch

Last edited by markadlerdallas. Register to edit

Tags: none

What is the line current of a 7 horsepower motor operating on 120 volts at full load, a power factor of 0.8, and 95% efficient?

  • 4.72 amps.
  • 13.03 amps.
  • 56 amps.
  • Correct Answer
    57.2 amps.

What is the line current of a 7 horsepower motor operating on 120 volts at full load, a power factor of 0.8, and 95% efficient?

57.2 amps.


NOTE: One (1) horsepower in electricity is the same as 746 Watts. Specifically, 746 is in Newton meters per second.

For more info, please see Basic Electrical Engineering site for proof of 1 hp = 746 watts


From wp2ahg:

Amps = ((( (746 x hp) / V ) / E.F ) / P.F ) =

\[{\text{Amps}}=\frac{\frac{\frac{{746}\times{\text{ Hp}}}{\text{Volts}}}{\text{Efficiency}}}{Power}\]

((( (746 x 7hp) / 120 volts) / 95%ef / .8pf) = 57.2 amps

\[{\text{Amps}}=\frac{\frac{\frac{{746\text{ W/Hp}}\times{7\text{ Hp}}}{120\text{Volts}}}{0.95\text{ Efficiency}}}{.08\text{ Power}}\] \[\text{Amps}={57.2\text{ amps}}\]

or

\begin{align} \text{Ohm's law: }\\ I &= \frac{P}{E}\\ Amps &= \frac{Watts}{Volts}\\ \\ \end{align}

\[\frac{746\text{ Watts/Hp}\times{7\text{ Hp}}}{120\text{ Volts}\times{0.95\text{ Efficiency}\times{0.8\text{ Power Factor}}}}\]

\[\text{Amps}={57.2\text{ amps}}\]

Last edited by markadlerdallas. Register to edit

Tags: none

A 3 horsepower, 100 V DC motor is 85% efficient when developing its rated output. What is the current?

  • 8.545 amps.
  • 20.345 amps.
  • Correct Answer
    26.300 amps.
  • 25.000 amps.

A 3 horsepower, 100 V DC motor is 85% efficient when developing its rated output. What is the current?

26.300 amps.

From wp2ahg:

\[\text{I}=\frac{746\text{ watts/Hp}\times \text{Hp}}{\text{ Volts}\times{\text{ Efficiency}\times{\text{Power Factor}}}}\]

[PF not given]

\[\text{I}=\frac{746\text{ watts/Hp}\times \text{3 Hp}}{100\text{ Volts}\times{0.85\text{ % Efficiency}}}\]

\[\text{I}=\frac{2,238\text{W/Hp}}{85\text{ Efficiency}}={26.3\text{ amps}}\]


NOTE: One (1) horsepower in electricity is the same as 746 Watts. Specifically, 746 is in Newton meters per second.

For more info, please see Basic Electrical Engineering site for proof of 1 hp = 746 watts

Last edited by markadlerdallas. Register to edit

Tags: none

The output of a separately-excited AC generator running at a constant speed can be controlled by:

  • The armature.
  • Correct Answer
    The amount of field current.
  • The brushes.
  • The exciter.

The output of a separately-excited AC generator running at a constant speed can be controlled by:

The amount of field current.

The field current can compensate for mechanical lags, heat, hardware conditions, etc.

For detailed explanation, please see the Science Direct site for the article on Rotor Excitation, particularly on section 0.3.4 Effect of VAR Control on AVR/Rotor Field Current

For info on key concepts, please see the U.S. Nuclear Regulatory Commission's pdf document on 9.0 GENERATOR, EXCITER, AND VOLTAGE REGULATION

For an overall info on Electrical AC Engines, please see Brown University site for pdf document on BASIC AC ELECTRICAL GENERATORS

Last edited by markadlerdallas. Register to edit

Tags: none